Delta T Conversion

Luciano 668 x 820 in White RAL 9010

Calculate the right radiator output for your heating system;

To ensure our rooms are heated correctly a calculation is used to establish how much heat is needed to maintain a comfortable temperature. This is referred to as heat output or heat loss and is measured in British Thermal Units (BTUs) or Watts.

Once we know how much heat we need we can then find the right size and number of radiators we need. All radiators are tested to confirm how much heat they give off, the calculation produces a result called a Delta T.

Delta T, or ∆T, specifically relates to the difference in temperature between the water circulating in the central heating system and that of the ambient or room temperature. If the ambient or room temperature is 20ºC and the mean water temperature inside the radiators is 70ºC, the Delta T or ∆T value is calculated as 70 ºC - 20 ºC = 50ºC.

Delta T 50° is the UK standard for all domestic gas boilers and is set to allow professionals, end-users and consumers alike, to make a fair and reasonable comparison of radiator and towel rail outputs from various suppliers and across a mix of product types. This test is based on a set of parameters that replicate the temperature of the water coming from the boiler/heat source (flow temperature), desired room temperature and the return temp of the water.

However, if any of these factors are changed it will affect the amount of heat given off by a radiator meaning you may need a different size. For example, if your flow temp is lower than 80 the radiator will provide less heat. With today’s new boilers and renewable heat sources, a lot of heating systems are producing a flow temperature of 55ºC or lower which will mean a delta T of 30 (less heat in = less heat out!).

Our simple conversion tool can tell you how much heat your chosen radiator will produce based on this new Delta T so you can find an alternative size if needed

Delta T Correction Factors - Delta T 50°

Delta T Conversion

B2-EN442 states all hydronic radiator and towel rail outputs are tested and presented at Delta T 50° or ΔT 50°. To calculate the output at a different Delta T, enter your output at Δt 50°C and select your required Delta T conversion.

Your Calculation Result

Having input your output at ΔT 50°, your correction value output is shown below. For correction factors at Delta T 60°, please use the additional table supplied below.

Require Delta
Converted Delta

When comparing products ensure you are being quoted Delta T 50°, furthermore look for the MARC logo (Manufacturers Association of Radiators and Convectors) and be sure to request the Declaration of Performance, conducted by an accredited body. 

 

A Delta T correction factor allows end-users and professionals to find out the actual output of a radiator or towel rail in the range of Delta T variations. The above calculator has been designed to efficiently calculate this based on input at Delta T 50°, alternatively, you can use the listed correction factors below, also based on Delta T 50°.

Delta T

Correction 

Factors

75°

1.69

70°

1.55

65°

1.41

60°

1.27

55°

1.13

50°

1

45°

0.87

40°

0.75

35°

0.63

30°

0.51

25°

0.41

20°

0.3

15°

0.21

10°

0.12

0.05

Example: Assuming a radiator or towel rail has a heat output of 1000 Watts at ΔT (Delta T) = 50°. At ΔT (Delta T) = 60°, the output would be 1000 x 1.27 (from the table above) equating to 1270 Watts. Alternatively, at ΔT (delta T) = 40°, the output would be 1000 x 0.75 equating to 750 Watts.

Delta T Correction Factors - Delta T 60°

Some older UK boiler systems operate at higher flow and return temperatures and therefore (albeit illegally) some suppliers/resellers may quote radiators and towel rail outputs at Delta T 60° only.

 

Where Delta T 60° is provided you can use the listed correction factors below, to find the actual output at Delta T 50° and below.

Delta T

Correction 

Factors

60°

1

55°

0.906

50°

0.787

45°

0.705

40°

0.605

35°

0.519

30°

0.43

25°

0.344

20°

0.262

15°

0.185

Example: Assuming a radiator or towel rail has a heat output that gives 1000 Watts at ΔT (delta T) = 60°. At ΔT (delta T) = 50°, the output would be 1000 x 0.787 (from the table above) equating to 787 Watts.